Rkc CB/CD/CH Series Pid Digital Temperature Controller Thermostat

Product Details
Customization: Available
Customized: Non-Customized
Certification: RoHS, ISO9001, CE
Still deciding? Get samples of US$ 1520/Piece
Order Sample
Shipping & Policy
Shipping Cost: Contact the supplier about freight and estimated delivery time.
Payment Methods:
visa mastercard discover JCB diners club american express T/T
PIX SPEI OXXO PSE OZOW
  Support payments in USD
Secure payments: Every payment you make on Made-in-China.com is protected by the platform.
Refund policy: Claim a refund if your order doesn't ship, is missing, or arrives with product issues.
Manufacturer/Factory, Trading Company
Secured Trading Service
Diamond Member Since 2011

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Registered Capital
500000 RMB
Plant Area
1001~2000 square meters
  • Rkc CB/CD/CH Series Pid Digital Temperature Controller Thermostat
  • Rkc CB/CD/CH Series Pid Digital Temperature Controller Thermostat
  • Rkc CB/CD/CH Series Pid Digital Temperature Controller Thermostat
  • Rkc CB/CD/CH Series Pid Digital Temperature Controller Thermostat
  • Rkc CB/CD/CH Series Pid Digital Temperature Controller Thermostat
  • Rkc CB/CD/CH Series Pid Digital Temperature Controller Thermostat
Find Similar Products

Basic Info.

Model NO.
CB
Display Type
LED
Input
Universal
Output
SSR, Relay or 4-20mA
Control
Pid
Control Type
Digital
Type
Temperature Controller
Transport Package
1PCS/Box
Specification
CE
Trademark
TRIHERO
Origin
China
HS Code
9032100000
Production Capacity
100000PCS/Year

Packaging & Delivery

Package Size
8.00cm * 8.00cm * 8.00cm
Package Gross Weight
0.200kg

Product Description

RKC CB Series PID Digital Temperature Controller
Rkc CB/CD/CH Series Pid Digital Temperature Controller Thermostat

 
  • Measurement accuracy: ±0.3% of displayed value
  • Sampling time: 0.5 sec.
  • Longtime seller of Temperature Controllers
  • Plug-in construction

Main specification

  • Number of Inputs :1 point
  • Input type : *See the Input Range Code for the input range.

1)Thermocouple : K, J, T, S, R, E, B, N, W5Re/W26Re, U, L, PLII

2)RTD: Pt100 or JPt100

3)DC voltage: 0 to 5V dc, 1 to 5V dc

4)DC current: 0 to 20mA dc, 4 to 20mA dc *A 250Ω external resistor is required.

  • Sampling time: 0.5 sec.
  • Measurement accuracy:±(0.3% of displayed value+1 digit) *Depends on the input and the range.
  • Outputs (OUT1)

1) Relay contact output : 1a contact

2) Voltage pulse output for SSR driving: 0/12V dc

3) DC Current output : 0 to 20mA, 4 to 20mA dc

4) Triac trigger output: Trigger method - Zero cross method

 

  • Output 2 (OUT2)  *Cooling output for heat/cool control

1) Relay contact output : 1a contact

2) Voltage pulse output for SSR driving: 0/12V dc

3) DC Current output : 4 to 20mA dc

  • Alarm outputs (max.2 points): Temperature alarm, Heater break alarm, and Control loop break alarm
  • CT input for Heater break alarm (max. 1 point)
  • Communication function: Communication interface RS-485

 

  • Power supply voltage (Rating): 100 to 240Vac/24Vac/24Vdc
  • Ambient temperature: 0 to 50°C
  • Weight:

CB100 Approx. 170g

CB400 Approx. 250g

CB500 Approx. 250g

CB700 Approx. 290g

CB900 Approx. 340g

  • Safety standards: UL UL61010-1

cUL CAN/CSA-22.2 NO.61010-1

CE Marking: Low Voltage Directive (LVD)EN61010-1